4.2.1.12 Technical revision history
Table 315: EFIPTOC Technical revision history
Technical revision
Change
B The minimum and default values changed to 40
ms for the
Operate delay time
setting
C Minimum and default values changed to 20 ms for
the
Operate delay time
setting
Minimum value changed to 1.00 x I
n
for the
Start
value
setting
D
Added a setting parameter for the "Measured Io"
or "Calculated Io" selection
E Internal improvement
F Internal improvement
Table 316: EFHPTOC Technical revision history
Technical revision Change
B Minimum and default values changed to 40 ms for
the
Operate delay time
setting
C Added a setting parameter for the "Measured Io"
or "Calculated Io" selection
D Step value changed from 0.05 to 0.01 for the
Time
multiplier
setting
E Internal improvement
F Internal improvement
Table 317: (F)EFLPTOC Technical revision history
Technical revision
Change
B The minimum and default values changed to 40
ms for the
Operate delay time
setting
C
Start value
step changed to 0.005
D Added a setting parameter for the "Measured Io"
or "Calculated Io" selection
E Step value changed from 0.05 to 0.01 for the
Time
multiplier
setting
F Internal improvement
G Internal improvement
Section 4 1MRS758755 A
Protection functions
278 REC615 and RER615
Technical Manual