Table 329: DEFHPDEF Input signals
Name Type Default Description
Io SIGNAL 0 Residual current
Uo SIGNAL 0 Residual voltage
BLOCK BOOLEAN 0=False Block signal for activating the blocking mode
ENA_MULT BOOLEAN 0=False Enable signal for current multiplier
RCA_CTL BOOLEAN 0=False Relay characteristic angle control
Table 330: DEFLPDEF Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
Table 331: FDEFLPDEF Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
Table 332: DEFHPDEF Output signals
Name
Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
4.2.2.11 Settings
Table 333: DEFLPDEF Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Start value 0.010...5.000 xIn 0.005 0.010 Start value
Start value Mult 0.8...10.0 0.1 1.0 Multiplier for scaling the start value
Directional mode 1=Non-directional
2=Forward
3=Reverse
2=Forward Directional mode
Time multiplier 0.05...15.00 0.01 1.00 Time multiplier in IEC/ANSI IDMT curves
Table continues on next page
1MRS758755 A Section 4
Protection functions
REC615 and RER615 305
Technical Manual