Parameter Values (Range) Unit Step Default Description
Operating curve type 1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
15=IEC Def. Time Selection of time delay curve type
Operate delay time 50...200000 ms 10 50 Operate delay time
Characteristic angle -179...180 deg 1 -90 Characteristic angle
Max forward angle 0...180 deg 1 80 Maximum phase angle in forward
direction
Max reverse angle 0...180 deg 1 80 Maximum phase angle in reverse
direction
Min forward angle 0...180 deg 1 80 Minimum phase angle in forward direction
Min reverse angle 0...180 deg 1 80 Minimum phase angle in reverse direction
Voltage start value 0.010...1.000 xUn 0.001 0.010 Voltage start value
Table 334: DEFLPDEF Group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Type of reset curve 1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate Selection of reset curve type
Operation mode 1=Phase angle
2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88
1=Phase angle Operation criteria
Enable voltage limit 0=False
1=True
1=True Enable voltage limit
Table 335: DEFLPDEF Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Curve parameter A 0.0086...120.0000 1 28.2000 Parameter A for customer programmable
curve
Curve parameter B 0.0000...0.7120 1 0.1217 Parameter B for customer programmable
curve
Table continues on next page
Section 4 1MRS758755 A
Protection functions
306 REC615 and RER615
Technical Manual