Parameter Values (Range) Unit Step Default Description
-23=Recloser E
(132)
-24=Recloser F
(163)
-25=Recloser G
(121)
-26=Recloser H
(122)
-27=Recloser J
(164)
-28=Recloser Kg
(165)
-29=Recloser Kp
(162)
-30=Recloser L
(107)
-31=Recloser M
(118)
-32=Recloser N
(104)
-33=Recloser P
(115)
-34=Recloser R
(105)
-35=Recloser T
(161)
-36=Recloser V
(137)
-37=Recloser W
(138)
-38=Recloser Y
(120)
-39=Recloser Z
(134)
Operate delay time 50...200000 ms 10 50 Operate delay time
Characteristic angle -179...180 deg 1 -90 Characteristic angle
Max forward angle 0...180 deg 1 80 Maximum phase angle in forward
direction
Max reverse angle 0...180 deg 1 80 Maximum phase angle in reverse
direction
Min forward angle 0...180 deg 1 80 Minimum phase angle in forward direction
Min reverse angle 0...180 deg 1 80 Minimum phase angle in reverse direction
Voltage start value 0.010...1.000 xUn 0.001 0.010 Voltage start value
Table 338: FDEFLPDEF Group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Type of reset curve 1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate Selection of reset curve type
Operation mode 1=Phase angle
2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88
1=Phase angle Operation criteria
Enable voltage limit 0=False
1=True
1=True Enable voltage limit