Table 344: DEFHPDEF Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
Minimum operate time 40...60000 ms 1 40 Minimum operate time for IDMT curves
Allow Non Dir 0=False
1=True
0=False Allows prot activation as non-dir when dir
info is invalid
Measurement mode 1=RMS
2=DFT
3=Peak-to-Peak
2=DFT Selects used measurement mode
Min operate current 0.005...1.000 xIn 0.001 0.005 Minimum operating current
Min operate voltage 0.01...1.00 xUn 0.01 0.01 Minimum operating voltage
Correction angle 0.0...10.0 deg 0.1 0.0 Angle correction
Pol reversal 0=False
1=True
0=False Rotate polarizing quantity
Io signal Sel 1=Measured Io
2=Calculated Io
1=Measured Io Selection for used Io signal
Uo signal Sel 1=Measured Uo
2=Calculated Uo
1=Measured Uo Selection for used Uo signal
Pol quantity 3=Zero seq. volt.
4=Neg. seq. volt.
3=Zero seq. volt. Reference quantity used to determine
fault direction
4.2.2.12 Monitored data
Table 345: DEFLPDEF Monitored data
Name
Type Values (Range) Unit Description
FAULT_DIR Enum 0=unknown
1=forward
2=backward
3=both
Detected fault direction
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
DIRECTION Enum 0=unknown
1=forward
2=backward
3=both
Direction information
ANGLE_RCA FLOAT32 -180.00...180.00 deg Angle between operating
angle and characteristic
angle
ANGLE
FLOAT32 -180.00...180.00 deg Angle between polarizing
and operating quantity
I_OPER FLOAT32 0.00...40.00 xIn Calculated operating
current
DEFLPDEF Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Section 4 1MRS758755 A
Protection functions
312 REC615 and RER615
Technical Manual