Table 346: FDEFLPDEF Monitored data
Name Type Values (Range) Unit Description
FAULT_DIR Enum 0=unknown
1=forward
2=backward
3=both
Detected fault direction
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
DIRECTION Enum 0=unknown
1=forward
2=backward
3=both
Direction information
ANGLE_RCA FLOAT32 -180.00...180.00 deg Angle between operating
angle and characteristic
angle
ANGLE
FLOAT32 -180.00...180.00 deg Angle between polarizing
and operating quantity
I_OPER FLOAT32 0.00...40.00 xIn Calculated operating
current
FDEFLPDEF Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 347: DEFHPDEF Monitored data
Name
Type Values (Range) Unit Description
FAULT_DIR Enum 0=unknown
1=forward
2=backward
3=both
Detected fault direction
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
DIRECTION Enum 0=unknown
1=forward
2=backward
3=both
Direction information
ANGLE_RCA FLOAT32 -180.00...180.00 deg Angle between operating
angle and characteristic
angle
ANGLE
FLOAT32 -180.00...180.00 deg Angle between polarizing
and operating quantity
I_OPER FLOAT32 0.00...40.00 xIn Calculated operating
current
DEFHPDEF Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS758755 A Section 4
Protection functions
REC615 and RER615 313