Multi-frequency admittance calculation
Multi-frequency admittance calculation module calculates neutral admittances
utilizing fundamental frequency and the 2nd, 3rd, 5th, 7th and 9th harmonic
components of residual current and zero-sequence voltage. The following
admittances are calculated, if the magnitude of a particular harmonic in residual
current and zero-sequence voltage are measurable by the protection relay.
Fundamental frequency admittance (conductance and susceptance)
Y
I
U
G j B
o o0
1
0
1
0
1
1 1
3
=
⋅
−
= + ⋅
GUID-565B235E-04DA-4AC2-93A8-FE327A53424F V1 EN (Equation 32)
The fundamental frequency neutral admittance phasor.
The fundamental frequency zero-sequence current phasor
( ( ) / )= + +I I I
A B C
1 1 1
3
The fundamental frequency zero-sequence voltage phasor
( ( ) / )= + +U U U
A B C
1 1 1
3
The fundamental frequency conductance,
The fundamental frequency susceptance,
Harmonic susceptance
Im ImY
I
U
j B
n
n
n
o
n
0
0
0
3
=
⋅
−
= ⋅
GUID-FEC1F705-F45C-4C56-9A74-AC4EDFC7FC4C V1 EN (Equation 33)
where n = 2, 3, 5, 7 and 9
The nth harmonic frequency neutral admittance phasor.
The nth harmonic frequency zero-sequence current phasor.
The nth harmonic frequency zero-sequence voltage phasor.
The nth harmonic frequency susceptance,
Section 4 1MRS758755 A
Protection functions
376 REC615 and RER615