8.1.6.4 Settings
Table 583: RESCMMXU Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
A Hi high limit res 0.00...40.00 xIn 1 0.20 High alarm current limit
A high limit res 0.00...40.00 xIn 1 0.05 High warning current limit
A deadband res 100...100000 1 2500 Deadband configuration value for integral
calculation. (percentage of difference
between min and max as 0,001 % s)
Table 584: RESCMMXU Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Measurement mode 1=RMS
2=DFT
2=DFT Selects used measurement mode
8.1.6.5 Monitored data
Table 585: RESCMMXU Monitored data
Name
Type Values (Range) Unit Description
Io-A FLOAT32 0.00...40.00 xIn Measured residual
current
BLOCK BOOLEAN 0=False
1=True
Block signal for all binary
outputs
HIGH_ALARM BOOLEAN 0=False
1=True
High alarm
HIGH_WARN BOOLEAN 0=False
1=True
High warning
I_INST_RES FLOAT32 0.00...40.00 xIn Residual current
Amplitude, magnitude of
instantaneous value
I_ANGL_RES
FLOAT32 -180.00...180.00 deg Residual current angle
I_DB_RES FLOAT32 0.00...40.00 xIn Residual current
Amplitude, magnitude of
reported value
I_DMD_RES
FLOAT32 0.00...40.00 xIn Demand value of residual
current
I_RANGE_RES Enum 0=normal
1=high
2=low
3=high-high
4=low-low
Residual current
Amplitude range
Max demand Io FLOAT32 0.00...40.00 xIn Maximum demand for
residual current