8.1.7.2 Function block
A070779 V2 EN
Figure 298: Function block
8.1.7.3 Signals
Table 588: RESVMMXU Input signals
Name Type Default Description
Uo SIGNAL 0 Residual voltage
BLOCK BOOLEAN 0=False Block signal for all binary outputs
Table 589: RESVMMXU Output signals
Name Type Description
HIGH_ALARM BOOLEAN High alarm
HIGH_WARN BOOLEAN High warning
8.1.7.4 Settings
Table 590: RESVMMXU Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
V Hi high limit res 0.00...4.00 xUn 1 0.20 High alarm voltage limit
V high limit res 0.00...4.00 xUn 1 0.05 High warning voltage limit
V deadband res 100...100000 1 10000 Deadband configuration value for integral
calculation. (percentage of difference
between min and max as 0,001 % s)
Table 591: RESVMMXU Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Measurement mode 1=RMS
2=DFT
2=DFT Selects used measurement mode
Section 8 1MRS758755 A
Measurement functions
572 REC615 and RER615
Technical Manual