Name Type Values (Range) Unit Description
STATUS Enum -1=Not defined
1=Ready
2=InProgress
3=Successful
4=WaitingForTri
p
5=TripFromProte
ction
6=FaultDisappe
ared
7=WaitToCompl
ete
8=CBclosed
9=CycleUnsucce
ssful
10=Unsuccessfu
l
11=Aborted
AR status signal for
IEC61850
INPRO_1 BOOLEAN 0=False
1=True
Reclosing shot in
progress, shot 1
INPRO_2 BOOLEAN 0=False
1=True
Reclosing shot in
progress, shot 2
INPRO_3 BOOLEAN 0=False
1=True
Reclosing shot in
progress, shot 3
INPRO_4 BOOLEAN 0=False
1=True
Reclosing shot in
progress, shot 4
INPRO_5 BOOLEAN 0=False
1=True
Reclosing shot in
progress, shot 5
DISCR_INPRO BOOLEAN 0=False
1=True
Signal indicating that
discrimination time is in
progress
CUTOUT_INPRO
BOOLEAN 0=False
1=True
Signal indicating that cut-
out time is in progress
SUC_RECL BOOLEAN 0=False
1=True
Indicates a successful
reclosing sequence
UNSUC_CB BOOLEAN 0=False
1=True
Indicates an
unsuccessful CB closing
CNT_SHOT1 INT32 0...2147483647 Resetable operation
counter, shot 1
CNT_SHOT2 INT32 0...2147483647 Resetable operation
counter, shot 2
CNT_SHOT3 INT32 0...2147483647 Resetable operation
counter, shot 3
CNT_SHOT4 INT32 0...2147483647 Resetable operation
counter, shot 4
CNT_SHOT5 INT32 0...2147483647 Resetable operation
counter, shot 5
COUNTER INT32 0...2147483647 Resetable operation
counter, all shots
SHOT_PTR INT32 1...7 Shot pointer value
Table continues on next page
Section 9 1MRS758755 A
Control functions
664 REC615 and RER615
Technical Manual