1MRS755225
Transformer Terminal
Technical Reference Manual, General
RET 54_
73
Default variation of
binary input change
event object
1...3 2
Default variation of
binary output object
1...2 2
Default variation of
counter object
1...2 1
Default variation of
counter event object
1...2 1
Default variation of
analog input object
1...2 1
Default variation of
analog input event
object
1...2 1
Default variation of
analog output status
object
1...2 1
Class 1 event delay 0...1000 [s] 1 Delay for spontaneous event reporting
for class 1
Class 1 event. count 1...32 1 Event count for spontaneous event
reporting for class 1
Class 2 event delay 0...1000 [s] 1 Delay for spontaneous event reporting
for class 2
Class 2 event count 1...32 1 Event count for spontaneous event
reporting for class 2
Class 3 event delay 0...1000 [s] 1 Delay for spontaneous event reporting
for class 3
Class 3 event count 1...32 1 Event count for spontaneous event
reporting for class 3
Unsolicited reporting
mode
2)
0...3
[0=unsolicited responses
are disabled;
1=send messages
immediately;
2 =first send empty UR and
wait for confirmation, then
send data filled URs;
3=first send empty UR and
wait for confirmation, wait
for enable UR from master
and then send data filled
URs]
0 Unsolicited messages reporting
behavior
Time synchronization
mode
0...2
[0=Never;
1=Periodic;
2=Startup]
2 See DNP 3.0 Remote Communication
Protocol for RET 54_ manual
(1MRS755260).
Baud rate 0...6
[0=300;
1=600;
2=1200;
3=2400;
4=4800;
5=9600;
6=19200]
5 Communication speed of DNP
protocol
Number of stop bits 1...2 1
Next character
timeout
0...65535 [ms]
1)
0
End of frame timeout
2....65535 [ms]
1)
10