EasyManua.ls Logo

ABB RET 545 - Page 31

ABB RET 545
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Underfrequency or overfrequency protection, 5 stages, Freq1St1… Freq1St5, f</f>, df/dt
Operation mode
Undervoltage limit for blocking
Start value for under-/overfrequency prot.
Operate time for under-/overfrequency prot.
Start value for df/dt protection
Operate time for df/dt protection
Not in use
f</f> 1 timer
f</f> 2 timers
f</f> OR df/dt>
f</f> AND df/dt>
f</f> OR df/dt<
f</f> AND df/dt<
0.30…0.90 x Un
25.00…75.00 Hz
0.10…120.00 s
0.2…10.0 Hz/s
0.12…120.00 s
Operation accuracy
- Frequency rate of change (df/dt):
- real df/dt
- real df/dt
- Undervoltage blocking
Start time:
- total start times at fn = 50 Hz:
- frequency measurement
- df/dt measurement
Reset time
Operate time accuracy
Under-/overfrequency (f</f>): ±10 mHz
<±5 Hz/s: ±100 mHz/s
<±15 Hz/s: ±2.0% of real df/dt
±1.0% of set value
<100 ms
<120 ms
140...1000 ms (depends on the minimum pulse width set
for the trip output)
±2% of set value or ±30 ms
Overexcitation protection, low-set stage, OE1Low, U/f>, and high-set stage, OE1High, U/f>>
U/f start (DT mode)
U/f start (IDMT mode)
U max cont.
Operate time
k
Maximum time
Constant delay
Cooling time
Operation mode
1.00...2.00 x U/f
1.00...2.00 x U/f
0.80...1.60 x Un
0.10...600.00 s
0.1...100.0
500...10000 s
0.1...120.0 s
5...10000 s
Not in use; Definite time; Curve#1; Curve#2
Operation accuracies
Start time:
- Injected U/f
- internal time
- total time
Reset time
Reset ratio:
- 20...40 Hz
- 40...80 Hz
Retardation time
Operate time accuracy at definite-time mode
Operate time accuracy at inverse-time modes
20...40 Hz: 4% of set value; 40...80 Hz: ±2% of set value
>2.0 x Un/fn
<60 ms,
<70 ms
100…1060 ms (depends on the set minimum pulse width
for the TRIP output)
typ. 0.99
typ 0.97
<105 ms
20...80 Hz: ±4% of set value or ±40 ms
±100 ms or the accuracy appearing when the measured
voltage varies ±1.0%
Transformer Terminal RET 541, RET 543, RET 545
1MRS755543