characteristic for the second time delay follows the similar formulas as for the first
time delay, but the t2 setting is used instead of t1.
Line voltage drop
SEMOD159053-105 v6
The purpose with the line voltage drop compensation is to control the voltage, not
at the power transformer low voltage side, but at a point closer to the load point.
Figure
73 shows the vector diagram for a line modelled as a series impedance with
the voltage U
B
at the LV busbar and voltage U
L
at the load center. The load current
on the line is I
L
, the line resistance and reactance from the station busbar to the
load point are R
L
and X
L
. The angle between the busbar voltage and the current, is
j. If all these parameters are known U
L
can be obtained by simple vector
calculation.
Values for R
L
and X
L
are given as settings in primary system ohms. If more than
one line is connected to the LV busbar, an equivalent impedance should be
calculated and given as a parameter setting.
The line voltage drop compensation function can be turned On/Off by the setting
parameter OperationLDC. When it is enabled, the voltage U
L
will be used by the
Automatic voltage control for tap changer function, TR1ATCC for single control
and TR8ATCC for parallel control for voltage regulation instead of U
B
. However,
TR1ATCC or TR8ATCC will still perform the following two checks:
1. The magnitude of the measured busbar voltage U
B
, shall be within the security
range, (setting Umin and Umax). If the busbar voltage falls-out of this range
the line voltage drop compensation calculations will be temporarily stopped
until the voltage U
B
comes back within the range.
2. The magnitude of the calculated voltage U
L
at the load point, can be limited
such that it is only allowed to be equal to or smaller than the magnitude of U
B
,
otherwise U
B
will be used. However, a situation where U
L
>U
B
can be caused
by a capacitive load condition, and if the wish is to allow for a situation like
that, the limitation can be removed by setting the parameter OperCapaLDC to
On.
1MRK 504 169-UEN A Section 11
Control
Transformer protection RET650 2.2 IEC 197
Application manual