Combined Overvoltage and Undervoltage Relay
Technical Reference Manual
REU 523
4.1.1.9. Self-supervision
The self-supervision system of the REU 523 manages run-time fault situations and
informs the user about an existing fault. When the self-supervision system detects a
permanent internal relay fault, the READY indicator LED will start to blink. At the
same time the self-supervision alarm relay (also referred to as the IRF relay), which
is normally picked up, will drop off and a fault code will appear on the LCD. The
fault code is numerical and identifies the fault type. For fault codes, refer to section
Internal fault in the Operator’s Manual.
)LJ ,QWHUQDOIDXOW
Fault codes can indicate:
• no response on the output contact test
• faulty program, work or parameter memory
• too high or too low a reference voltage value
4.1.2. Measurements
The table below presents the measured values which can be accessed through the
HMI, expressed as multiples of the rated voltage, U
n
, of the energizing input.
Faultc
C
E
STARTREADY TRIP
INTERNAL FAULT
FAULT CODE :56
Table 4.1.2-1 Measured values
Indicator Measured data
U
12
Main voltage U
12
U
23
Main voltage U
23
U
31
Main voltage U
31
U
1s
Positive-phase-sequence voltage
U
max
Maximum voltage of the three main voltages
U
min
Minimum voltage of the three main voltages
U
1min
Average voltage of the three main voltages during one minute
U
10min
Average voltage of the three main voltages during ten minutes