1MRS 750942-MUM
Combined Overvoltage and Undervoltage Relay
Technical Reference Manual
REU 523
27
)LJ 2XWSXWVLJQDOPDWUL[
New trip indication timer
The new trip indication timer can be configured to allow a second trip indication on
the LCD. When several protection stages trip, the first trip indication will be
displayed until the time, as specified by the “NEW TRIP IND.” setting value, has
expired. After this, a new trip indication can displace the old one. The basic
protection functions are not affected by the “NEW TRIP IND.” setting.
Table 4.1.4.6-7 SGR1...SGR8
Switch Function
Default
setting
SGR1/1...4 U> signal to output contacts PO1, PO2, SO1 and SO2 12
SGR2/1...4 t> signal to output contacts PO1, PO2, SO1 and SO2 3
SGR3/1...4 U>> signal to output contacts PO1, PO2, SO1 and SO2 12
SGR4/1...4 t>> signal to output contacts PO1, PO2, SO1 and SO2 3
SGR5/1...4 U< signal to output contacts PO1, PO2, SO1 and SO2 12
SGR6/1...4 t< signal to output contacts PO1, PO2, SO1 and SO2 3
SGR7/1...4 U<< signal to output contacts PO1, PO2, SO1 and SO2 12
SGR8/1...4 t<< signal to output contacts PO1, PO2, SO1 and SO2 3
Table 4.1.4.6-8 New trip indication timer
Setting Description
Setting
range
Default
setting
New trip indication New trip indication timer in minutes 0...998 60
No new trip indication allowed until the
previous one has been manually cleared
999
128
1
U>
t>
1
2345678
2345678
1
U>>
t>>
1
2345678
2345678
1
U<
t<
1
2345678
2345678
1
U<<
t<<
1
2345678
2345678
1248 163264
O_S_U5_3
Checksum
(factory setting)
PO1
PO2
SO
1
SO2
Not in use
Not in use Not in use
Not in use
SGR1
SGR1=
(12)
SGR2=
(3)
SGR2
SGR3=
(12)
SGR4=
(3)
SGR5
SGR5=
(12)
SGR6=
(3)
SGR7
SGR7=
(12)
SGR8=
(3)
SGR3
SGR4
SGR6
SGR8
Weighting factor