36
1MRS 750942-MUM
Combined Overvoltage and Undervoltage Relay
Technical Reference Manual
REU 523
Table 4.1.10.2-1 Information mapping of configuration set 1
Event reason
Event code
Function
type
Information
number
Standard description of
the information number
(IEC 60870-5-103)
GI
Relative
time
Type
identification
PO1
Activated/Reset
E17/
E18
160 27 auxiliary input 1 X - 1
PO2
Activated/Reset
E19/
E20
160 28 auxiliary input 2 X - 1
SO1
Activated/Reset
E21/
E22
160 29 auxiliary input 3 X - 1
SO2
Activated/Reset
E23/
E24
160 30 auxiliary input 4 X - 1
Table 4.1.10.2-2 Information mapping of configuration set 1
Measurand
Normalize
factor
Rated value
Function
type
Information
number
Standard description of
the information number
(IEC 60870-5-103)
Type
identification
Current I
L2
(not
measured
)
-
-
160 145 measurand I 3.2
Voltage U
12
2.40 U
n
7DEOH ,QIRUPDWLRQPDSSLQJRIFRQILJXUDWLRQVHW
Event reason
Event code
Function
type
Information
number
Standard description of
the information number
(IEC 80870-5-103)
GI
Relative
time
Type
identification
U> Start
Activated/Reset
E1/
E2
165 84 - X E1 2
U> Trip
Activated/Reset
E3/
E4
165 90 - - E1 2
U>> Start
Activated/Reset
E5/
E6
165 94 - X E5 2
U>> Trip
Activated/Reset
E7/
E8
165 91 - - E5 2
U< Start
Activated/Reset
E9/
E10
166 84 - X E9 2
U< Trip
Activated/Reset
E11/
E12
166 90 - - E9 2
U<< Start
Activated/Reset
E13/
E14
166 94 - X E13 2