152 | RMC-100| 2105552MNAE
Figure 7-36: Analog inputs 1 and 2 after calibration
4. Select Factory from the Calibration drop-down list for the appropriate AI (Figure 7-37
).
Figure 7-37: Reset AI calibration back to factory defaults
5. Click Send.
6. Repeat the calibration procedure in section 7.1.2
, Analog input calibration (voltage mode), or
section 7.1.3, Analog input calibration (current mode).