*HQHUDO,QIRUPDWLRQDQG,QVWDOODWLRQ8VHU¶V*XLGH
6HFWLRQ$ 7%7%0RGXOH%XV&DEOH$GDSWHU2XW,Q
3BSE 020 923R101 111
$ 7%7%0RGXOH%XV&DEOH$GDSWHU 2XW,Q
)HDWXUHV
• Passive unit used for connection and extension of the
ModuleBus
• DIN rail mounting.
'HV FULSWLRQ
The TB805 ModuleBus Cable Adaptor-Out and TB806
ModuleBus Cable Adaptor-In with the ModuleBus
Extension Cables, TK801V0xx, are used to extend the
ModuleBus.
Using the TB805 and TB806, I/O modules on the same
electrical ModuleBus of an I/O cluster, can be mounted
on different DIN rails. This makes the installation of I/O
Modules more flexible when laying out an enclosure
design. Please refer to Section 2.1.4.1, I/O Station with
S800 I/O for details on layouts.
The ModuleBus extension cables used with the
TB805/TB806 comes in 3 standard lengths:
• VTK801V003 - 300 mm
• TK801V006 - 600 mm
• TK801V012 - 1.2 meters.
Overall ModuleBus length must not exceed 2.5 meters
including all cables and MTUs.
The TB805/TB806 mounts on the standard DIN rail.
It has a mechanical latch that locks it to the rail. It is
grounded to the DIN-rail through a metallic spring
connector. The latch can be released with a screwdriver.
DB25 Female
Connector (X2)
TB805 ModuleBus
Connector (X1)
14
1
13
25
DB25 Male
Connector (X2)
TB806 ModuleBus
Connector (X1)
1
13
14
25