*HQHUDO,QIRUPDWLRQDQG,QVWDOODWLRQ8VHU¶V*XLGH
$SSHQGL[$ 5HIHUHQFHV
112 3BSE 020 923R101
7 HFKQLFDO'DWD
7 DEOH $ 7%7%0RGXOH%XV&DEOH$GDSWRU6SHFLILFDWLRQV
,WHP 7% 7%
Direction Out In
Connections 2
DIN41612 Type R/4 (X1)
DB25 Female (X2)
2
DIN41612 Type R/4 (X1)
DB25 Male (X2)
ModuleBus:
Maximum 5V current distribution
Maximum 24V current
distribution
1.5A
1.5A
1.5A
1.5A
Module catch Locks module to previous
device
Locks module to previous device
Module DIN rail lock Locks module and provide
ground connection
Locks module and provide
ground connection
Safety Classification Class I according to IEC 536;
(earth protected)
Class I according to IEC 536;
(earth protected)
Protection Rating IP20 according to IEC 529,
(IEC 144)
IP20 according to IEC 529, (IEC
144)
Rated Insulation Voltage 50V 50V
Dielectric test voltage 500V a.c. 500V a.c.
Width 22 mm (0.88”) 22 mm (0.88”)
Depth 25 mm (0.98”) 25 mm (0.98”)
Height 109 mm (4.3”) 109 mm (4.3”)
Weight 55 g (0.12 lbs.) 55 g (0.12 lbs.)