AUP: auxiliary position contacts
The AUP contacts are intended for circuit-breakers in withdrawable version.
They electrically signal the position of a moving part (inserted/test/withdrawn) in relation to the fixed part in
which they are inserted.
These are "switching" contacts and are available, up to a maximum of six contacts per circuit-breaker, in the
following configurations:
• six standard contacts
• six digital signals
The following table provides information on the electrical characteristics:
Characteristics Standard Digital signals
Breaking
capacity
DC
24V - 0.1 A
125V 0.5A @ 0ms / 0.3A @ 10ms -
250V 0.3A @ 0ms / 0.15A @ 10ms -
AC
250V
3A cos φ 0,3 -
5A cos φ 0,7 -
5A cos φ 1 -
400V
3A cos φ 1 -
2A cos φ 0,7 -
1A cos φ 0,3 -
Minimum load 50mA @ 24V 1mA @ 5V
AUP: Connections
Further information is available on page 58, or on the site http://www.abb.com/abblibrary/DownloadCenter/,
where the wiring diagram is available 1SDM000091R0001.
95
A4
A3
XF
XF
A4
151
154
151
154
S75I/2
42
1
152
152
141
144
141
144
S75I/1
42
1
142
142
131
132
131
132
S75T/2
24
1
134
134
121
122
121
122
S75T/1
24
1
124
124
111
112
111
112
S75E/2
24
1
114
114104
104
S75E/1
24
1
102
101
102
101
Diagram 95