ABB SACE SACE PR010/T RH0025002 L2551 19/20
20
4 Problems updating
the software
installed on the
PR010/T unit
Wrong connection cable
used to connect the PC
to the PR010/T test unit
Replace with the cable supplied
and repeat the operation
The serial cable is not
properly connected
Make sure the cable connectors
are properly inserted
The PR010/T unit is not
ready for Sw updating
Proceed as described under the
heading "Sw updating
procedures"
The PR010/T's time-out
elapses before the
software starts
downloading from the PC
Make sure the PR010/T unit
displays the message "Waiting for
update" at the start of the file
transfer procedure
The update file is not
selected
Select the required software
version and repeat the update
procedure
The wrong type of file is
selected
Select file type PR010t_x.Hex
The file downloaded is
damaged
Use a spare copy or download
the updated software version
from our Internet site
5 Problems
downloading the
test report to the PC
Wrong connection cable
used to connect the PC
to the PR010/T test unit
Replace with the cable supplied
and repeat the operation
The serial cable is not
properly connected
Make sure the cable connectors
are properly inserted
6 Problems
connecting the
cable to the device
under test
The PR111-type release
is fitted with the wrong
adapter
Fit the correct PR111 adapter
The PR111 adapter is
damaged
Replace with the spare one
supplied
A cable for the Isomax
series is connected to an
Emax circuit breaker, or
vice versa
Use the correct cable for the
circuit breaker
Troubleshooting guide