ERROR MESSAGES, TROUBLESHOOTING
Updating of faults described in chap. 6.7 of Instruction RH0025002:
Difficulties in
updating PR010/T:
- Display locked on
“updating”.
- Display locked on
start-up screen.
During an update could be
caused by:
- Power outage.
- Cable between PR010/T
and PC has detached.
- Driver of serial line to PC
is locked.
1. Shut down PR010/T and remove
power supplier if connected.
2. Restart PR010/T.
3. Press STOP button within 2s from
powering: this will prepare unit for
re-programming.
4. Comply with instructions on
display.