EasyManua.ls Logo

ABB SF6 LTB 245E1 BLG 1002A - Page 86

ABB SF6 LTB 245E1 BLG 1002A
231 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operating and Maintenance Instructions
Inspection intervals
1HSB435409-100 en1 15
8c.
Dashpot 15 years or 5,000 mechanical
Close-Open operations.
Checking of oil-level or recording of
damping during operation alternatively.
Recording of damping during operation
is made by means of a circuit breaker
analyzer with transducers connected to:
main shaft of the circuit breaker
mechanism when checking the
opening dash-pot
main shaft (cam shaft) of the
operating mechanism when
checking the closing dash-pot.
These measurements are to be carried
out only by specially trained personal.
See Manual 1HSB515409-100 for BLG
1002A or 1HSB535409-100 for BLK
222.
8d.
Catch-gears 15 years or 5,000 mechanical
Close-Open operations.
Visual control of the adjustment.
Play of gaps in the catch-gears acc. to
Manual 1HSB515409-100 for BLG
1002A or 1HSB535409-100 for BLK
222.
Greasing of shafts and catch surfaces
with Grease “L” acc. to 1HSB445409-1.
Change the signal from coil 1 to coil 2.
8e.
Coils 15 years or 5,000 mech CLOSE/
OPEN operations.
The resistances of coils and coil
currents are allowed to differ +/- 10%
from value measured at routine test.
8f.
Mechanical interlocking
Only applicable for BLG
1002A
15 years or 5,000 mech. CLOSE/
OPEN operations.
In OPEN position the distance between
the interlocking arm and the
interlocking disc shall be min. 2 mm.
In CLOSE position there must be full
contact between the arm and disc (No
gap is permitted).
See Manual 1HSB515409-100.
To be inspected Inspection interval Measures / Instructions / Tools

Table of Contents