EQS TEMPERATURE TRANSMITTER
CREATE/MODIFY CONFIGURATION
C - 2
Key Display Comments
Select NEW to create a new configuration. To mo d i f y
an existing configuration, select MODIFY. The
screen sequence is the same, however, the MODIFY
screens will appear with the values and cursor posi-
tions as originally configured.
Select ABB FSK.
Use the right arrow key to select EQS.
Enter a name for the configuration ID tag using up to
14 ASCII characters. To select a character, press the
key that has the desired character. Continue to press
the key until the desired character appears. Use the
right arrow key to move to the next character. Use the
left arrow key to go back to the previous character.
For this example select ANALOG.
For this example select T/C.
Select N type.
Choose the desired temperature unit.
CONFIG
CONFIGURATION
→ NEW
MODIFY
ERASE
ENTER
DEVICE TYPE
→ ABB FSK
HART
ENTER
TRANSMITTER TYPE
PTS → EQS
BCN EQN
AVS TB480 cond
ENTER
STT04 CONFIGURATION
[]
←PREVIOUS NEXT→
ENTER
SELECT MODE:
→ ANALOG
DIGITAL
ENTER
SENSOR TYPE:
→ T/C RTD
mV OHMS
ENTER
THERMOCOUPLE
→ NBE
JKR
STC
ENTER
ENGINEERING UNIT
→
o
C
o
F
o
K