PTH PRESSURE TRANSMITTER
CALIBRATION
D - 7
Select UPDOWN ARROW KEYS.
NOTE: Refer to METER VALUE ADJUSTMENT for
details about meter value entry.
Adjust transmitter output using the up and down
arrow keys. If configured digitally this adjust display
does not appear.
NOTE: When increasing or decreasing the mA sig-
nal, the increments of change increase with succes-
sive depressions until the maximum level of change
is reached. By changing direction the smallest incre-
ment of change returns. This technique speeds up
the adjustment process without affecting fine
adjustment.
Adjust the transmitter output using the up and down
arrow keys.
Key Display Comments
ENTER
D/A CAL USING
→UPDOWN ARROW KEYS
METER VALUE ENTRY
ENTER
ADJUST TO 4 mA
THEN HIT ENTER
ENTER
ADJUST TO 20 mA
THEN HIT ENTER
ENTER
ID TAGNAME
READY