TZID/AZH POSITIONER
CREATE/MODIFY CONFIGURATION
M - 4
Use the stroke range to further reduce the valve
range given by the valve stops.
A percentage of the input current where the zero
point occurs.
Monitors the control deviation. If the valve can not be
positioned correctly within the deadband time limit,
an error message is generated.
Specify time using the number keypad. This parame-
ter provides electronic damping of the valve stroke
movement and limits stroke speed to the specified
value.
Low and high alarm limits are user configurable
alarms.
NOTE: Use
to return to a previous configura-
tion screen from any screen in the configuration pro-
cess.
Select YES.
Key Display Comments
ENTER
MIN STROKE RANGE:
0.00 %
MAX STROKE RANGE:
100.00 %
ENTER
SHUT-OFF VALUE
(0 - 20 %)
nn.nn %
ENTER
DEADBAND TIME LIMIT
(0 - 200 sec)
n.nn sec
ENTER
ADJUSTED TIME, UP
nn.nn sec
ADJUSTED TIME, DOWN
nn.nn sec
ENTER
LOW ALARM LIMIT
nn.nn %
HIGH ALARM LIMIT
nn.nn %
BACK
ENTER
STORE THIS
CONFIGURATION?
NO
YES
ENTER
ID TAGNAME
READY