600T & 600T EN PRESSURE TRANSMITTER
CALIBRATION
Q - 24
PV Bias
The PV Bias calibration procedure allows you to align the "zero" of
the process with the "zero" reading of the transmitter. This may be
done in one of two ways:
• Apply a pressure that corresponds to the desired zero offset or
bias [SET PV ZERO]
• To scale to a value different from zero, calculate the offset or
biasand apply it to the 600T EN [SET PV VAL]
Use the number keys to enter the current meter
reading.
Use the number keys to enter the current meter
reading.
Key Display Comments
ENTER
4 mA CALIBRATION:
ENTER METER VALUE
n.nnnn
ENTER
20 mA CALIBRATION:
ENTER METER VALUE
nn.nnnn
ENTER
ID TAGNAME
READY
Key Display Comments
This operation will cause a change in output not cor-
responding to the input. Be sure the control loop is in
manual.
Select YES.
CALI-
BRATE
ENTER
OUTPUT WILL BE
AFFECTED! PROCEED?
NO
→ YES