EasyManuals Logo

ABB Switchsync F236 User Manual

ABB Switchsync F236
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
Controlled Switching — Buyer´s Guide
D-4
Edition 2, 2006-09
Application Capacitor Banks and Harmonic Filters
Switching of Capacitor Banks and Harmonic Filters
Suitable Switchsync
TM
Controllers
Only closing: Switchsync™ E113
Three-pole Operated and Mechanically Staggered Circuit Breakers
Single-pole Operated Circuit Breakers
Only closing: Switchsync™ F236
Legend:
R,S,T Three-phase busbar
C
in
Closing command input
O
in
Opening command input
U
ref
Reference voltage input
C
out
Closing command output
O
out
Opening command output
Both closing and opening: Switchsync™ F236
Both closing and opening: Switchsync™ E213
Suitable conditions for combined controlled open-
ing and controlled closing exist for ungrounded
capacitor banks. The need for controlled opening of
grounded capacitor banks is low.
R
S
T
Switchsync
F236
O
in
C
in
O
out
C
out
U
ref
Load:
Shunt C apacitor or
Harmonic Filter
R
S
T
Load:
Shunt Capacitor or
Harmon ic Filter
Switch sync
E113
C
in
C
out
U
ref
R
S
T
Switchsync
E213
O
in
C
in
O
out
C
out
Load:
Shunt Capacitor or
Harmonic Filter
U
ref
The purpose of the CT secondary feedback signal is
for adaptation control.
All examples are shown with reference in phase T.
However, any voltage with a known phase shift can
be used as a reference.
R
S
T
Switchsync
F236
C
in
C
out
U
ref
Load:
Shunt Capacitor or
Harmonic Filter

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Switchsync F236 and is the answer not in the manual?

ABB Switchsync F236 Specifications

General IconGeneral
BrandABB
ModelSwitchsync F236
CategoryController
LanguageEnglish