Technical Data Technical Information
Technical Data for Switchsync
TM
Type of controller E113 and E213 F236 L183 T183
Power supply
Power consumption
110 - 250 V AC/DC
< 4 VA
110 - 250 V AC/DC
< 4 VA
110 - 250 V AC/DC
< 4 VA
110 - 250 V AC/DC
< 4 VA
Operating command
Duration
48 - 250 V DC
0.15 - 2 s
48 - 250 V DC
0.15 - 2 s
48 - 250 V DC
0.15 - 2 s
48 - 250 V DC
0.15 - 2 s
Reference voltage detector
Power consumption
35 - 150 V AC ,15 - 66 Hz
< 0.1 VA
35 - 150 V AC, 15 - 66 Hz
< 0.1 VA
35 - 150 V AC, 45 - 66 Hz
< 0.1 VA
35 - 150 V AC, 15 - 66 Hz
< 0.1 VA
Current start detector
Short-time current
Power consumption
0.5 - 5.0 A
100 A, 1 s
0.66 VA at 5.0 A
0.5 - 5.0 A
100 A, 1 s
0.66 VA/input at 5.0 A
- -
Voltage start detector
Power consumption
AC
DC
48 - 250 V AC/DC
< 1.5 VA
< 0.2 VA
48 - 250 V AC/DC
< 1.5 VA/input
< 0.2 VA/input
48 - 250 V DC
-
< 0.2 VA/input
48 - 250 V DC
-
< 0.2 VA/input
Trip information
Power consumption
- -
48 - 250 V DC
< 0.2 VA
48 - 250 V DC
< 0.2 VA
CB status detector
Power consumption
- -
48 - 250 V DC
< 0.2 VA
48 - 250 V DC
< 0.2 VA
Load voltage input
Input impedance
- -
55-70 or 100-120 V AC
> 200 kΩ
55-70 or 100-120 V AC
> 200 kΩ
Cross-section area of
connecting leads
4 mm
2
4 mm
2
4 mm
2
4 mm
2
Socket screws
Hollow socket screws for easy plug-in connection of recording device during commissioning tests.
Ambient temperature
-30 - +55 °C -30 - +55 °C -30 - +55 °C -30 - +55 °C
Immunity tests
Power interruption test
IEC 60255-11
IEC 61000-4-11
EN 61000-4-11
IEC 61000-4-11
EN 61000-4-11
IEC 61000-4-11
EN 61000-4-11
Power frequency withstand 2
kV, 1 min.
IEC 60255-5 IEC 60255-5 IEC 60255-5 IEC 60255-5
Surge/Transients
IEC 60255-4 Cl. III
IEC 61000-4-5
EN 61000-4-5
IEC 61000-4-5
EN 61000-4-5
IEC 61000-4-5
EN 61000-4-5
Burst/Fast transients
IEC 60255-22-4 Cl. IV
EN 50082-2
IEC 61000-4-4
EN 61000-4-4
IEC 61000-4-4
EN 61000-4-4
IEC 61000-4-4
EN 61000-4-4
1 MHz burst transient
IEC 60255-22-1 Cl. III IEC 60255-22-1 Cl. III IEC 60255-22-1 Cl. III IEC 60255-22-1 Cl. III
Electrostatic discharge
EN50082-2
(IEC 60801-2)
IEC 61000-4-2
EN 61000-4-2
IEC 61000-4-2
EN 61000-4-2
IEC 61000-4-2
EN 61000-4-2
Radiated electro-magnetic
field
IEC 60801-3
(EN50082-2)
IEC 61000-4-3
EN 61000-4-3
IEC 61000-4-3
EN 61000-4-3
IEC 61000-4-3
EN 61000-4-3
Conducted radio frequency
interference
EN 50081-2
EN 61000-4-6
IEC 61000-4-6
EN 61000-4-6
IEC 61000-4-6
EN 61000-4-6
IEC 61000-4-6
Vibrations
IEC 60068-2-29 IEC 60068-2-29 IEC 60068-2-29 IEC 60068-2-29
Emission tests
Conducted and radiated
emission
EN 50081-2
EN 55011A
CISPRI11A
EN 55011A
CISPRI11A
EN 55011A
CISPRI11A
Dimensions
146 x 146 x 298 mm 146 x 290 x 298 mm 146 x 290 x 298 mm 146 x 290 x 298 mm