18 OI/TTR200-EN Rev. B | TTR200
9.4 Parameter descriptions
DTM menu path, parameters Description
<Device> / <Extras>
<Write Protection> Activates write protection for the entire device
— Yes: locked
— No: unlocked
— Enter password: 0110
<Device reset> Configuration data is reset to factory settings (see "Factory settings" on page 19)
<Factory reset> Configuration data is reset to factory settings (see "Factory settings" on page 19).
The adjustment data Trim high / low and DAC adjustment values are also reset to factory settings.
— Yes / OK
<Device> / <Configuration>
<Sensor / Sensor type> Selects sensor type:
— Pt100 (IEC751)
— Pt1000 (IEC751)
— Thermocouple type K (IEC584)
— Thermocouple type B (IEC584)
— Thermocouple type C (ASTME988)
— Thermocouple type D (ASTME988)
— Thermocouple type E (IEC584)
— Thermocouple type J (IEC584)
— Thermocouple type N (IEC584)
— Thermocouple type R (IEC584)
— Thermocouple type S (IEC584)
— Thermocouple type T (IEC584)
— Thermocouple type L (DIN43710)
— Thermocouple type U (DIN43710)
— Thermovoltage –125 … 125mV
— Thermovoltage –125 … 1100mV
— Resistance 0 …. 500
— Resistance 0 …. 5000
— Pt10 (IEC751)
— Pt50 (IEC751)
— Pt200 (IEC751)
— Pt500 (IEC751)
— Pt10 (JIS1604)
— Pt50 (JIS1604)
— Pt100 (JIS1604)
— Pt200 (JIS1604)
— Pt10 (IMIL24388)
— Pt50 (IMIL24388)
— Pt100 (MIL24388)
— Pt200 (MIL24388)
— Pt1000 (MIL24388)
— Ni50 (DIN43760)
— Ni100 (DIN43760)
— Ni120 (DIN43760)
— Ni1000 (DIN43760)
— Cu10 (OIML R 84), a=4270
— Cu100 (OIML R 84), a=4270
<Sensor / Connection> Sensor connection type relevant for all Pt, Ni, Cu resistance thermometers
— Two-wire: sensor connection type in two-wire technology
— Three-wire: sensor connection type in three-wire technology
— Four-wire: sensor connection type in four-wire technology
<Sensor / Line resistance> Sensor line resistance relevant for all Pt, Ni, Cu resistance thermometers with a two-wire circuit
Value range: 0 ... 100 Ω