TZIDC, TZIDC-200 DIGITAL POSITIONER | COI/TZIDC/TZIDC-200-EN REV. B 11
Parameter description HART®
Parameter
Display
Function
Possible parameter
setting
Unit
Factory setting
P1._
STANDARD
P1.0
ACTUATOR
Actuator type
Actuator type
LINEAR, ROTARY
---
LINEAR
P1.1
AUTO_ADJ
Auto
adjust
Autoadjust
Function
---
---
P1.2
ADJ_MODE
Auto adjust mode
Automatic adjustment mode
FULL,STROKE,CTRL_PAR, ZERO_POS, LOCKED
FULL
P1.3
TEST
Test
Test
Function
---
INACTIVE
P1.4
FIND_DEV
Find device
Find device
DISABLE, ONE TIME, CONTINOUS
---
DISABLE
P1.5
EXIT
Return
Return to operating level
Function
---
NV_SAVE
P2._
SETPOINT
P2.0
MIN_RGE
Min
setpoint range
Min. setpoint range
4.0
to 18.4
mA
4.0
P2.1
MAX_RGE
Max setpoint range
Max. setpoint range
20.0 to 5.6
mA
20.0
P2.2
CHARACT
Charact.
curve
Characteristic curve
LINEAR
, 1:25, 1:50, 25:1, 50:1, USERD
---
LINEAR
P2.3
ACTION
Valve action
Direction of action
DIRECT, REVERSE
---
DIRECT
P2.4
SHUT_CLS
Shut
-off value 0%
Shut
-off value 0 %
OFF,
0.1 to 45.0
%
1.0
P2.5
SHUT_OPN
Shut off value 100%
Shut-off value 100%
55.0 to 100.0, OFF
%
OFF
P2.6
RAMP
UP
Set
point ramp, up
Setpoint ramp (up)
OFF,
0 to 200
---
OFF
P2.7
RAMP DN
Set point ramp, down
Setpoint ramp (down)
OFF, 0 to 200
---
OFF
P2.8
EXIT
Return
Return to operating level
Function
---
NV_SAVE
P3._
ACTUATOR
P3.0
MIN_RGE
Min.
of stroke range
Operating range, min.
0.0
to 90.0
%
0.0
P3.1
MAX_RGE
Max. of stroke range
Operating range, max.
100.0 to 10.0
%
100
P3.2
ZERO_POS
Zero
position
Zero position
CLOCKWISE,
CTCLOCKWISE
---
CTCLOCKWISE
P3.3
EXIT
Return
Return to operating level
Function
---
NV_SAVE
P4._
MESSAGES
P4.0
TIME_OUT
Control time out
Dead band time limit
OFF, to 200
---
OFF
P4.1
POS_SW1
Position
switch 1
Switching point SW1
0.0
to 100.0
%
0.0
P4.2
POS_SW2
Position switch 2
Switching point SW2
0.0 to 100.0
%
100.0
P4.3
SW1_ACTV
Switchpoint
1 enable
Active direction SW1
FALL_BEL,
EXCEED
---
FALL_BEL
P4.4
SW2_ACTV
Switchpoint 2 enable
Active direction SW2
FALL_BEL, EXCEED
---
EXCEED
P4.5
EXIT
Return
Return to operating level
Function
---
NV_SAVE
P5._
ALARMS
P5.0
LEAKAGE
Leakage
detection
Leakage to actuator
ACTIVE,
INACTIVE
---
INACTIVE
P5.1
SP_RGE
Setpoint rng monitor
Outside the setpoint range
ACTIVE, INACTIVE
---
INACTIVE
P5.2
SENS_RGE
Sens.
range monitor
Operating range
exceeded
ACTIVE,
INACTIVE
---
INACTIVE
P5.3
CTRLER
Controller monitor
Controller inactive
ACTIVE, INACTIVE
---
INACTIVE
P5.4
TIME_OUT
Control
time out
Dead band time limit
ACTIVE,
INACTIVE
---
INACTIVE
P5.5
STRK_CTR
Stroke counter
Movement counter
ACTIVE, INACTIVE
---
INACTIVE
P5.6
TRAVEL
Travel
counter
Travel counter
ACTIVE,
INACTIVE
---
INACTIVE
P5.7
EXIT
Return
Return to operating level
Function
---
NV_SAVE

Table of Contents

Other manuals for ABB TZIDC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB TZIDC and is the answer not in the manual?

ABB TZIDC Specifications

General IconGeneral
Input Signal4 to 20 mA
Communication ProtocolHART
Protection ClassIP66, NEMA 4X
Enclosure RatingIP66, NEMA 4X
Operating Temperature-40 to 85 °C
MaterialAluminum
MountingLinear or rotary actuators
Housing MaterialAluminum
Weight1.5 kg
Supply Pressure1.4-7 bar (20-100 psi)