23
Circuit-breaker nameplate
Note: Each panel is fitted with two circuit-breaker
nameplates which are located:
inside the low voltage compartment door
on the circuit-breaker (not visible from outside)
Figure 48: Circuit-breaker nameplate.
5.3 Storage
If the apparatus has to be stored before installation,
suitable packing must be provided.
On receipt, the switchgear must be unpacked and
checked as described in “Control on receipt” (chapter
5.2).
In the case of storage, the switchgear must be packed
up again using the original materials. The switchgear
must be stored in a dry, dust-free, noncorrosive place,
at a temperature between 5 °C to + 45 °C and not
affected by any significant variations.
If this is not possible, store the switchgear in a well-
ventilated room, cover the apparatus with tarpaulins or
waterproof sheets (e.g. polyethylene) and provide
anti-condensation heaters. The package contains
dehydrating bags that must be replaced every six
months.
Please do not hesitate to contact ABB for any further
information.