3. Technical data
3.1 Electrical data
Rated power frequency withstand voltage
Rated power frequency over isolation distance
Rated lightning impulse withstand voltage
Rated lightning impulse withstand voltage over isolation distance
Rated short time withstand current 3s
Internal arc withstand current 1s
Branch connection rated current
Main busbar rated current
3.2 Resistance to internal arc faults
The fault withstand capacity is as follows:
IEC version: 31.5 kA x 1 s
ENA version: 25 kA x 1 s
The switchgear units have been tested according to
IEC 62271-200 Standards (appendix A, accessibility
type A, criteria 1 to 5) and also to ENATS 41-36. In
individual cases, depending on the configuration of
the switchgear panels and/or the switchgear room
conditions (e.g. low ceiling height), additional
measures may be necessary to ensure compliance
with criterion 1.