ZENITH ZTS(D) T-SERIES 1600-3000 A & ZTSCT T-SERIES 100-3000 A
6.3 Information
LCD
Touch
Message Description
Invalid Date Date not set
Test on Load Test on load sequence active
Test off Load Test off load sequence active
Alarm/Product Availability Digital output function activated
In Position I Digital output function activated
In Position O Digital output function activated
In Position II Digital output function activated
Pre-transfer Signal 1 Digital output function activated
Pre-transfer Signal 2 Digital output function activated
Pre-transfer Signal 3 Digital output function activated
Pre-transfer Signal 4 Digital output function activated
Source 1 Available Digital output function activated
Source 2 Available Digital output function activated
Load Shed Digital output function activated
Emergency Stop Digital input function activated
Remote Test on Load Digital input function activated
Remote Test off Load Digital input function activated
Inhibit ATS Digital input function activated
Manual Retransfer Digital input function activated
Priority S1 Digital input function activated
Priority S2 Digital input function activated
Inhibit Transfer Digital input function activated
Bypass Running Delays Digital input function activated
Remote Control to S1 Digital input function activated
Remote Control to Off Digital input function activated
Remote Control to S2 Digital input function activated
Alarm Reset Digital input function activated
Manual-Auto Mode Digital input function activated
Table 6.3 Info statements in level 3 and 4, LCD and touch control interfaces