4
ABB Zenith
ZTSCT / ZBTSCT Operation & Maintenance Manual
Installation
(contd)
NOTE: When the voltage and frequency
reach preset values, the Source 2
Available LED will illuminate.
7. Verify the phase to phase voltages at Source 2
line terminals.
8. Verify that the phase rotation of
Source 2 is the same as the phase
rotation of Source 1.
9. Shut down the generator’s engine.
(Place in Automatic Mode.)
NOTE: Source 2 Available LED will turn off.
NOTE: The engine generator will continue
to run for the duration of Source 2
Stop Delay Timer.
10. Place the disconnect switch to ENABLE.
11. Complete the visual inspection of the
transfer switch.
12. Close the enclosure.
13. Lock the enclosure.
Figure 5 LCD and keypad
After all options and accessories are checked and verified,
follow these steps to set up the ATS. Refer to Entelli-Switch
250 display Figure 5. The annunciation LEDs illuminate
to indicate (1) source availability, (2) ATS position, and
(3) Entelli-Switch 250 control function (timing).
1. Unlock the enclosure.
2. Open the enclosure.
3. Place the Disconnect Switch in the Inhibit.
NOTE: This step is only performed if the
“DS” Option was purchased.
4. Close the external (up-stream) Source 1
circuit breaker.
NOTES: Source 1 Available and Source 1
Position LEDs will illuminate.
If Source 1 Available LED does not
illuminate, verify that Source 1 Voltage
is above the preset restore value.
The Gen-Set will start and run while
Source 2 stop Delay Timer is timing.
5. Close the External (up-stream) Source 2 line
circuit breaker.
6. Start the engine generator in
MANUAL mode.
When performing a hi-pot or
dielectric test on the power section,
DISCONNECT the control panel plugs from
the microprocessor to avoid potential damage.
S1 O K
21:56
MON 23 APR 2008
MORE TEST
WARNING
Figure 4
Certain accessories, per specific
schematics, can inhibit automatic transfer.
Engine Gen-Set could start when
engine control wires are attached.
Initial Energization
(contd)
CAUTION
SERIAL NUMBER:
RA
TING: VOLTS -
AMPS -
SYSTEM VOLTS:
MODEL NUMBER:
HZ -
PHASE -
ABB Zenith