29
IE1-1230-B February 2001
Group 6 Option 8 Communicator Format
The Accord xpC panel has three communicator format options:
0. Comms disabled.
1. High Speed.
2. Contact I.D.
This option defaults to 1 (High Speed).
0 = Comms Disabled
If Option 8 Communicator Format is set to 0 the panel will not dial-out. Setting Option 8
Communicator Format to 0 (Comms Disabled) does not erase the Comms programming.
Communication can be restored with the previous programming by selecting 1-High speed.
1 = High Speed (8 channel)
If Option 8 Communicator Format is set to 1 the panel reports using 8 channel Ademco
Fast Format.
The system reports the triggers as detailed below:
Fire zones report using Code 1 in Channel 1 and Restore using Code 3 in
Channel 1.
PA, PA Silent and Duress zones report using Code 1 in Channel 2 and restore
using Code 3 in Channel 2.
Alarm zones report using Code 1 in Channel 3 and restore using Code 3 in
Channel 3.
Open (Unset) zones report using Code 2 in Channel 4 and Closing (Set) signals
report using Code 4 in Channel 4. The process of Setting and Unsetting can be
inverted using Group 9 - Option 2 (Invert Open/Close).
Tamper zones report using Code 1 in Channel 5 and restore using Code 3 in
Channel 5 when the system is unset. When the system is set Tamper zones report
using Code 1 in Channel 3 and restore using Code 3 in Channel 3.
Abort zones report using Code 1 in Channel 7.
Verified Alarm zones report using Code 1 in Channel 8. A Verified Alarm is two
alarm conditions during one set period that are separated by no more than the
Verified Alarm Time Window (default) 45 minutes. The alarm conditions must
come from separate zones.
Battery Low/AC Mains Loss and Test report in the status channel (Channel 9).