52
Note: Due to continued product development and improvements these specifications
may change without notice.
Remote Keypad Specification
Connected via a three wire terminal block on the back of the keypad.
Built in piezo warning sounder
Physical Width: 120 mm
Height: 120 mm
Depth: 25 mm
Electrical Voltage Input: 12 V d.c.
Current Drain: 50 mA (typical), 100 mA (maximum)
Appendix B: Connecting a Printer to the System
Installing a Printer
Two printer leads are required to connect the Accord xpC panel to a serial printer.
1. Master Printer Lead (part no. 2011-095) connects from the printer to the Adapter
Printer Lead.
2. Adapter Printer Lead (part no. 2011-096) connects from the control panel to the to
the Master Printer Lead.
The Adapter Printer Lead connects to the control panel using a 3 wires connection:
Yellow wire to LS terminal
Red wire to +Aux(12V)
Black wire to -Aux(0V)
The serial printer should have the following setting:
Baud Rate 1200 Data Bits 8
Parity None Start Bits 1
Stop Bits 2