General Data - Heat pump (R407C)
ACC 75DR ACC 100DR
A4MC 75ER A4MC 100ER
Btu/h 75000 100000
W 21960 29310
Btu/h 84000 110000
W 24600 32240
W 7706 11040
W 7706 9279
A 13.80 19.00
A 13.80 19.60
V/Ph/Hz 380 - 415 / 3 / 50 380 - 415 / 3 / 50
W/W 3.12 2.80
W/W 3.49 3.70
l/s / CFM 1142 / 2420 1487 / 3150
l/s / CFM 1156 / 2450 1477 / 3130
l/s / CFM 944 / 2000 1340 / 2840
l/s / CFM 793 / 1680 1057 / 2240
EXTERNAL STATIC PRESSURE (SH/H/M/L) Pa (in.wg.)
dBA 52 / 52 / 48 / 43 55 / 54 / 52 / 48
mm/in 430 / 16.9 430 / 16.9
mm/in 1426 / 56.1 1655 / 65.2
mm/in 826 / 32.5 826 / 32.5
mm/in 612 / 24.1 612 / 24.1
mm/in 1535 / 60.4 1765 / 69.5
mm/in 974 / 38.3 974 / 38.3
kg/lb 92 / 203 119 / 262
mm/in 25.4 / 1.0 25.4 / 1.0
l/s / CFM
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb 170 / 374 184 / 405
LIQUID mm/in 12.7 / 1/2 15.9 / 5/8
GAS mm/in 25.6 / 1-1/8 25.6 / 1-1/8
kg/lb 7.00 / 15.43 7.80 / 17.20
BRAZING
DUCTED
SLM WIRED HANDSET
196 / 137 / 98 / 69 (0.79 / 0.55 / 0.39 / 0.28)
3304 / 7000
64
1041 / 40.98
1150 / 45.3
1224 / 48.2
1175 / 46.3
REFRIGERANT CHARGE
INDOOR UNIT
DEPTH
UNIT WEIGHT
PIPE CONNECTION
TYPE
SIZE
HEIGHT
PACKING DIMENSION
AIR FLOW
OUTDOOR UNIT
WIDTH
UNIT WEIGHT
CONDENSATE DRAIN SIZE
UNIT DIMENSION
SOUND PRESSURE LEVEL
PACKING DIMENSION
WIDTH
DEPTH
HEIGHT
HEIGHT
WIDTH
DEPTH
HIGH
MEDIUM
SOUND PRESSURE LEVEL (SH/H/M/L)
UNIT DIMENSION WIDTH
DEPTH
LOW
NOMINAL RUNNING CURRENT (HEATING)
HEIGHT
AIR FLOW
SUPER HIGH
CONTROL
AIR DISCHARGE
OPERATION
REFRIGERANT CONTROL (EXPANSION DEVICE)
EER
COP
MODEL
OUTDOOR UNIT
POWER SOURCE
REFRIGERANT TYPE
INDOOR UNIT
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
NOMINAL RUNNING CURRENT (COOLING)
NOMINAL TOTAL INPUT POWER (COOLING)
NOMINAL TOTAL INPUT POWER (HEATING)
R407C
981 / 38.62
981 / 38.62
INDOOR & OUTDOOR TXV
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35.0°C DB / 23.9°C WB OUTDOOR
b) HEATING - 21.1°C DB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND
1m BELOW THE UNIT.
5) EER/COP CALCULATION IS BASED ON EFFECTIVE POWER INPUT AS PER ISO 5151.