69
Performance Data AWM-G-2009
2
nd
Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition: 23°C DB, 15°C WB
Outdoor Condition: 35°C DB
Indoor DB˚C Indoor WB˚C
Outdoor DB, ˚C
35
TC (kW) SC (kW)
........
........
20 15
...........................................
2.558 1.403
23 15
x
3
y
3
24 15 2.558 1.990
Total capacity, TC
x
3
= 2.558kW (Same as Total capacity at 20°C Indoor DB / 15°C Indoor WB & 35°C Outdoor WB)*
Sensible capacity, SC
Interpolation Method:
24º C – 20º C
=
1.990kW – 1.181kW
24º C – 23º C 1.990kW – y
3
y
1
= 1.844kW
(b) Indoor Condition: 23°C DB, 15°C WB
Outdoor Condition: 40°C DB
Indoor DB˚C Indoor WB˚C
Outdoor DB, ˚C
40
TC (kW) SC (kW)
........
........
20 15
...........................................
2.355 1.215
23 15
x
4
y
4
24 15 2.355 1.802
Total capacity, TC
x
4
= 2.355kW (Same as Total capacity at 20°C Indoor DB / 15°C Indoor WB & 40°C Outdoor WB)*
Sensible capacity, SC
Interpolation Method:
24º C – 20º C
=
1.597kW – 0.963kW
24º C – 23º C 1.597kW – y
4
y
2
= 1.655kW
* This is due to 2 different conditions with same WB temperature, will have the same level of enthalpy. For more
details, please refer to psychrometrics chart