EasyManuals Logo

Acson AWM 15GR User Manual

Acson AWM 15GR
165 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #80 background imageLoading...
Page #80 background image
78
3
rd
Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition: 23°C DB, 15°C WB
Outdoor Condition: 37°C DB
Total capacity, TC
Interpolation Method:
x = 2.477kW
Sensible capacity, SC
Interpolation Method:
y = 1.768kW
40°C - 35°C
=
2.355kW - 2.558kW
40°C - 37°C 2.355kW - x
40°C - 35°C
=
1.655kW - 1.844kW
40°C - 37°C 1.655kW - y
Outdoor DB ° C
Indoor DB Indoor WB 35 37 40
° C ° C TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW)
23 15 2.558 1.844 xy2.355 1.655
Downloaded from AC-Manual.com Manuals

Other manuals for Acson AWM 15GR

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Acson AWM 15GR and is the answer not in the manual?

Acson AWM 15GR Specifications

General IconGeneral
BrandAcson
ModelAWM 15GR
CategoryAir Conditioner
LanguageEnglish

Related product manuals