EasyManua.ls Logo

AEG PROTECT 1.100 - Page 13

AEG PROTECT 1.100
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13
Overload behaviour Up to 105% continuous;
with mains supply > 105% – < 130% for 10 min.
130% for 1
s
Following this, automatic,
uninterrupted switchover to
integrated bypass (SBS).
Switch-off after 1 min if overload
continues to be present. (Switch
back if overload decreases = load <
90%)
Overload behaviour with Up to 105% continuous;
battery operation > 105% for 10 s
Short-circuit behaviour 2.5 x I
N
for 100 ms
Battery
Standby times with external standard battery units
Standby times (full load / half load) [min.]
Coupled
battery cubicles
PROTECT
1.100
PROTECT
1.150
PROTECT
1.200
Recharging time
to 90% capacity
1 x PROTECT 1.100 BP 16 / 42 --- --- 5h
2 x PROTECT 1.100 BP 42 / 97 --- --- 7h
3 x PROTECT 1.100 BP 60 / 134 --- --- 10h
1 x PROTECT 1. BP 20 19 / 47 10 / 29 6 / 19 5h
2 x PROTECT 1. BP 20 47 / 103 29 / 68 19 / 47 9h
3 x PROTECT 1. BP 20 78 / 77 47 / 103 34 / 62 13h
4 x PROTECT 1. BP 20 103 / 243 68 / 153 47 / 103 18h
5 x PROTECT 1. BP 20 138 / 312 85 / 202 63 / 138 24h
Nominal DC voltage (intermediate circuit): 240 VDC
Trickle charge voltage: 274 VDC ± 1%
Battery charging current (max.): 4.2 ADC
Type Sealed, maintenance-free
PROTECT 1.100 BP 2x20 blocks 12V 9Ah,
e.g. CSB HR 1234WF2
PROTECT 1.BP20 1x20 blocks 12V 20Ah,
e.g. Panasonic LC-X1220P

Table of Contents