EasyManua.ls Logo

AEG PROTECT 1 Series - Page 43

AEG PROTECT 1 Series
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
43
Bypass
Line Inverter
Battery
This so-called passive redundancy protects against the total
failure of the voltage supply on the secured busbar; however, in
this operating mode, mains faults would directly affect the load.
As a result, the electronics continuously attempt to switch back
to "online" / normal operating mode (e.g. when the overload or
overtemperature goes away).
The bypass consists of an inverse-parallel thyristor stack and
functions as an extremely rapidly switching link between a load
and the mains. The synchronization unit ensures that the
frequency and phase of the inverter voltage is synchronized
with the mains and can therefore be switched over without
interruption (within the tolerance limits).
i
The bar graph LED functions as the display of
the UPS capacity utilisation. The acoustic signal
sounds every 2 seconds during this operating
mode.

Table of Contents

Related product manuals