24
If the surround is made of wood; remove the corner pieces and the plastic sleeve
rst. The UPS will be unpacked on the pallet, to lower it, suitable means (fork
truck, crane, hoist) must be used that can operate within the safety tolerance
limits for the approximate weights displayed in tables 5 and 6 (Page 73 75).
4.2.2. STORAGE
Equipment should be stored in a dry, ventilated place protected from rain,
splashing water and chemicals. It is recommended to store the UPS and batteries
in their original packing. This offers the best protection during transport and stor-
age.
If ordered with the UPS, closed lead accumulators are built into the UPS or
the battery cabinet. To ensure problem free operation of the 10 20 kVA
equipment you should not store for longer than 3 months and absolutely no
longer than 6 months.
If longer storage is required, the batteries must be recharged after the
aforementioned periods
Store batteries or equipment with built-in batteries at 20 25 °C.
Deviation from this may result in a reduction of maximum storage availability.
4.2.3. TRANSPORTATION TO SITE
All UPSs aretted with rollers to facilitate transport to site. Be sure to observe
tables 5 and 6 (page 73 75) for indicated weights in the selection of an
appropriate site and the selection of transport route (floor, elevators, stairs etc.)