3.4 Technical Data
Type power
PROTECT C. 1000 R (S) 1000 VA (cos = 0.7 lag.)
700 W
PROTECT C. 2000 R (S) 2000 VA (cos = 0.7 lag.)
1400 W
PROTECT C. 3000 R (S) 3000 VA (cos = 0.7 lag.)
2100 W
PROTECT C. 6000 R 6000 VA (cos = 0.7 lag.)
4200 W
UPS Input
Rated input voltage 220 / 230 / 240 Vac
Voltage tolerance range
C. 1000 R (S) – C. 3000 R (S) 160 Vac – 300 Vac ± 5 Vac
Bypass 80 Vac – 264 Vac
C. 6000 R 176 Vac – 276 Vac ± 3 %
Bypass 176 Vac – 261 %
Nominal frequency 50 Hz / 60 Hz
(automatic detection)
Frequency tolerance range ± 4 Hz
Curr. consumption (full load)
PROTECT C. 1000 R (S) 7 A
PROTECT C. 2000 R 10 A
PROTECT C. 2000 R S 12 A
PROTECT C. 3000 R (S) 16 A
PROTECT C. 6000 R 31 A
Input power factor
C.
1000 R (S) – C. 3000 R (S) ≥ 0.96
C.
6000 R ≥ 0.98
Connection
C.
1000 R (S) – C. 3000 R (S) non-heating
appliance connector
C.
6000 R Terminal block
15