11
EN
2.3 Technical Data
Type rating
PROTECT D.1000 1000 VA (pf = 0.9 lag.)
900 W
PROTECT D.1500 1500 VA (pf = 0.9 lag.)
1350 W
PROTECT D.2000 2000 VA (pf = 0.9 lag.)
1800 W
PROTECT D.3000 3000 VA (pf = 0.9 lag.)
2700 W
UPS input 1ph~ / N / PE
Nominal input voltage 230 Vac
Rectifier voltage range 190 Vac – 276 Vac
(PROTECT D.1000 & D.1500)
200 Vac – 276 Vac
(PROTECT D.2000 & D.3000)
Rectifier voltage range 180 Vac – 276 Vac
(PROTECT D.1000 & D.1500)
190 Vac – 276 Vac
(PROTECT D.2000 & D.3000)
Rectifier voltage range 160 Vac – 276 Vac
(PROTECT D.1000 & D.1500)
180 Vac – 276 Vac
(PROTECT D.2000 & D.3000)
Bypass voltage range 195.5 Vac – 253 Vac
Frequency 50 Hz / 60 Hz
(autom. recognition or manual)
Frequency tolerance range ± 5 Hz
Charging rate at full load and battery charging (max.)
PROTECT D.1000 4.8 A
PROTECT D.1500 7.2 A
PROTECT D.2000 9.6 A
PROTECT D.3000 13.7 A
Circuit feedback factor > 0.99
(without battery operation
100% load, pf = 0.9 lag.)
(without battery operation
100% load, pf = 0.8 lag.)
(without battery operation
100% load, pf = 0.7 lag.)

Related product manuals