4.2 Mains connection general
information
Read the Safety instructions regarding backfeed protection requirements.
Recommended protective devices, cable cross-sections, and
recommended upstream protection is advised in this section.
Recommended u
pstream circuit
breaker
Protect D 6000
LCD
C
curve,
2p
63A
Protect D 10000
LCD
C
curve,
2p
100A
Recommended cable cross-sections
Protect D 6000
LCD
Protect D 10000LCD
Protective earthing
conductor
Min cross section
6mm
2
(8AWG)
10mm
2
(6AWG)
Input L, N, G
Min conductor cross
section
6mm
2
(8AWG)
10mm
2
(6AWG)
Input fuse
80A
100A
Output L,
N,
Min conductor cross
section
6mm
2
(8AWG)
10mm
2
(6AWG)
Battery cable*
6mm
2
(8AWG)
10mm
2
(6AWG)
N(L2)
to UPS Normal AC / Bypass AC