66
Charger Fail
Fault (Red) LED is
flashing
1 beep every 1
second
Code: 34
Indicates that the
UPS has confirmed
the charger has failed
The UPS turns off the
charger until the next
power recycle.
Contact your service
representative
Battery Over Voltage
Fault (Red) LED is On.
Beep continuous.
Code: 68
Indicates that the
battery voltage is too
high
The UPS will turn off
the charger until the
battery voltage is
normal
Negative power Fault
Fault (Red) LED is On.
Beep continuous.
Code: 131
In parallel system
power of UPS is
negative
Redundancy mode is
on, the fault UPS turn
to fault mode
without output
Increase mode
UPS1& UPS2 turn to
fault mode
Parallel cable loss
Fault (Red) LED is On.
Beep continuous.
Code: 130
In parallel system
parallel cable
disconnected
Disconnect
parallel
cable one turn to
fault mode
Parallel system
battery status
Fault (Red) LED is
flash
1 beep every 1
second
Code: 134
UPS1 connect battery
UPS2 without battery
Check battery
connect status