oPERating conditions
mEssagE in English
dEscRiPtion
noRmal woRking status
Power off No display
PV inverter is totally shutdown,
V
PV
<= 90 V
Standby STANDBY 90 V < Input voltage <= 100 V
Initialization &
waiting
READY
Input voltage range 100 ~ 150 V during
start-up. After PV voltage is higher than
100 V, inverter is waiting for feeding
to grid
Check grid CHECKINGxxxs
If PV voltage > 150 V, inverter is che-
cking feeding conditions
Feeding to grid, MPPT GRID CONNECTED
Inverter is feeding power. After 10
seconds of this display, LED will show
wattage.
FLASH FLASH FLASH firmware
Today energy Etoday=xxx.xxkWh Total energy fed to grid since today
monitoRing PaRamEtERs
Instantaneous
Output power
Pac=xxx.xW Real time output power in xxxx W
Accumulated energy
information
Etot=xxxxxxkWh
Total energy fed to grid since inverter
was installed
Grid voltage Vac=xxx.xV Grid voltage in xxx.x VAC
Grid frequency Fac=xx.xHz Grid frequency in xx.x Hz
Feeding current Iac=xx.xA Feeding current amount in xx.x A
PV array voltage Vdc=xxx/xxx/xxxV Input voltage from PV array, xxx.x VDC
PV array current Idc=x.x/x.x/x.xA Input current from PV array, x.x Idc
systEm fault
Isolation failure ERR ISOLATION
Earth fault of the PV-panels or failure of
surge voltage protection
GFCI active ERR GROUND FAULT
Leakage current on ground conductor
too high
Grid failure ERR GRID
Grid measured data is beyond the spe-
cification (voltage & frequency)
No utility NO GRID Grid is not available
Input voltage too high DC OVERVOLTAGE Input voltage higher than the 450 V
6.5 lcd disPlay mEssagEs