Non-Contact, High Voltage Detector 275HVD
9
The following information provides typical detection distances when using
a lower setting than the line voltage.
Note that the distances may vary with each unit and will be affected based
on the actual environment. The values displayed were conducted in an
ideal lab environment and cannot represent each eld environment.
SETTING VOLTAGE DISTANCE
240VAC 500VAC 12" - 32cm
240VAC 1kVAC 18" - 48cm
240VAC 2kVAC 29" - 75cm
240VAC 6kVAC 48" - 124cm
240VAC 11kVAC 57" - 146cm
240VAC 22kVAC 89" - 226cm
SETTING VOLTAGE DISTANCE
2kVAC 6kVAC 16" - 40cm
2kVAC 11kVAC 20" - 52cm
2kVAC 22kVAC 24" - 60cm
2kVAC 33kVAC 36" - 92cm
SETTING VOLTAGE DISTANCE
6kVAC 11kVAC 24" - 61cm
6kVAC 22kVAC 29" - 75cm
6kVAC 33kVAC 41" - 105cm
SETTING VOLTAGE DISTANCE
11kVAC 22kVAC 13" - 35cm
11kVAC 33kVAC 16" - 42cm
SETTING VOLTAGE DISTANCE
22kVAC 33kVAC 14" - 36cm