Precision Air Conditioning
SmartCool
TM
– D
Precision Air Conditioning
135
Installation, Maintenance and Commissioning Manual :6877419 02/2013
Electrical Data – W2F0 Continued
SC25D067-W2F0-0 SC25D073-W2F0-0 SC25D080-W2F0-0
Standard Dry Cooler Match 1 x DR95 1 x DR95 1 x DR95 (EC)
Unit Data Full Function - W2F0
Nominal Run Amps (1) A 87.3 88.7 96.4
Maximum Start Amps A 231.1 226.1 268.9
Recommended Mains Fuse Size A 100 100 125
Max Mains Incoming Cable Size mm² 35 35 35
Mains Supply V 400V / 3PH + N / 50Hz
Control circuit VAC 24 24 24
Unit Data Cooling Only- W2F0
Nominal Run Amps A 61.5 64.4 75.9
Maximum Start Amps A 205.3 201.8 248.4
Recommended Mains Fuse Size A 80 80 100
Evaporator Fan Motor - Per Fan
Motor Type AC AC AC
Quantity x Motor Size (2) kW 3 x 2.38 3 x 2.38 3 x 2.38
Full Load Amps A 5 5 5
Locked Rotor Amps A 17.5 17.5 17.5
Compressor 1 , Circuit 1
Motor Size (3) kW 10.86 12.15 13.73
Nominal Run Amps A 19.2 20.7 24.5
Locked Rotor Amps A 163 158 197
Type of Start Direct On Line
Compressor 2, Circuit 1
Motor Size (3) kW 10.86 12.15 13.73
Nominal Run Amps A 19.2 20.7 24.5
Locked Rotor Amps A 163 158 197
Type of Start Direct On Line
Standard Dry Cooler Match - Motor Per Fan
AC AC EC
Quantity x Motor Size kW 4 x 0.88 4 x 0.88 4 x 1.68
Full Load Amps A 1.65 1.65 2.6
OPTIONAL EXTRAS
Electric Heating
Number of stage of Reheat 3 3 3
Number of Elements 9 9 9
Rating (Total) kW 31.5 31.5 31.5
Current Per Phase A 45.47 45.47 45.47
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25
Full Load Amps A 16.2 16.2 16.2
First upgrade Fan Motor - EC Motor - Per Fan
Quantity x Motor Size (2) kW 3 x 2.2 3 x 2.2 3 x 2.2
Full Load Amps A 3.3 3.3 3.3
Locked Rotor Amps A 3.3 3.3 3.3
Second upgrade Motor - EC Motor - Per Fan
Quantity x Motor Size (2) kW 3 x 3.1 3 x 3.1 3 x 3.1
Full Load Amps A 4.8 4.8 4.8
Locked Rotor Amps A 4.8 4.8 4.8
Standard Dry Cooler Match - EC Motor-Per Fan
Quantity x Motor Size (2) kW 4 x 1.68 4 x 1.68 N/A
Full Load Amps A 2.6 2.6 N/A
Dry Cooler Match - SCAF Fan
Quantity x Motor Size (2) kW 4 x 1.94 4 x 1.94 4 x 1.94
Full Load Amps A 3.4 3.4 3.4
(1) Values given for function units with standard selections for heating, humidification, supply air fans 7°C evaporating and 54.4°C condensing.
(2) Stated motor power is based on maximum electrical power absorbed
(3) Values are per compressor
W2F0